SUMMARY:Analysis on the Impact of the Cooling Water Temperature on the Oak
 forest-PACS System and Facility
DESCRIPTION:Research Poster\n\nAnalysis on the Impact of the Cooling Water
  Temperature on the Oakforest-PACS System and Facility\n\nNonaka, Hanawa, 
 Shoji\n\nHot water cooling approach [1] has been established as one of the
  standard techniques to improve the energy efficiency of modern HPC/Data C
 enters. However, to fairly evaluate its efficiency, there is a need to tak
 e into consideration not only the energy reduction of the cooling faciliti
 es, but also some possible negative impacts on the HPC system side. In thi
 s poster, we present some preliminary results of an investigation using th
 e Oakforest-PACS (OFP) system and facility using three temperature cases (
 9oC, 12oC, and 18oC). . As preliminary analysis results, we could confirm 
 that better PUE (1.25 -> 1.20 -> 1.18) and COP (4.26 -> 6.23 -> 8.72) can 
 be obtained by using higher temperature settings. However, we could also p
 erceive some performance degradation on the HPC system nodes, due to the f
 requency throttling mechanism, when using high temperature settings (18oC)
 . A more detailed analysis is part of our future works, which also include
  the impact on the energy consumption of the HPC system side.\n\n[1] S. Zi
 mmermann, et al., Aquasar: A hot water cooled data center with direct ener
 gy reuse. Energy. 43. 237–245.\n\nTag: Pre-Recorded